batchTREAT |
|
40 to 10,000 GPM |
|
Acid Wastes Neutralization Systems |
![]()
Acid Wastes Neutralization System
batchTREAT BT500
Duplex Batch Acid Wastes Neutralization System for the neutralization of acid and base industrial wastewater

Our duplex batch pH adjustment systems are, as with all of our systems, completely automated pH neutralization systems that are fabricated and tested in our factory prior to shipping. The duplex batching systems include the following features:
Flows in excess of 10,000 GPM
Redundancy of all critical components
Suitable for outdoor installation including UV protection and freeze protection
Self-diagnostics
The most sophisticated pH control available in industry
Bulk storage and distribution of acid and caustic used for neutralization
Ability to neutralize concentrated acid wastes and caustic wastes.
Modular / Skid Mounted Design except for the large treatment tanks.
Process Flow Diagram of a typical Duplex Batch Acid Waste Neutralization System

Layout of a typical Duplex Batch Acid Waste Neutralization System (shown without the optional catwalk)

| System Performance Specifications : | Influent Characteristics : Flow
0-1000, 500 GPM Peak Sustained Flow. Influent pH 0-14 pH units. Temperature 32-140 F. Effluent Characteristics : Flow, Discharged in batch volumes of up to 8,500 gallons / batch at flows up to 1500 gpm. pH Nominal discharge range is 6.50 - 8.50 pH units. (Actual discharge limit is field programmable). Effluent Monitoring : As mandated by the local controlling authority the effluent quality must be continuously monitored. A two pen recorder is to be used to monitor effluent flow rate and pH. The recorder is to be equipped with a flow totalizer. Any effluent pH deviations will trigger an alarm and system discharge will be halted. |
| batchTREAT
pH Adjustment systems are designed for the
purpose of acid wastes neutralization and caustic wastes neutralization of
any industrial wastewater stream. All systems within our
batchTREAT family are capable of
neutralizing acids and neutralizing bases of any pH and from any source. For
the neutralization of concentrated acids and concentrated bases our systems
are equipped with temperature monitoring and water quenching to control the
exothermic reactions.
All of our acid waste neutralization systems are completely automated and require no operator intervention other than periodic maintenance and calibrations. All of our batchTREAT acid waste neutralization system sized from 100 GPM and up are duplex batch system featuring two identical systems operating in parallel yet independently of one another other than intersystem communications. This provides complete redundancy of all critical system components. |
|
| Utilities, Weight, Dimensions : | Electrical : 480VAC, 3phase,
60hz, 30 amp. Disconnect not required, provided on MCP. Air : Less than 5 SCFM @ 80 PSIG. No special requirements for air quality. Dimensions : 24' x 30' x 16'(h). Access to the front of the skid and the both sides is required for ease of service. Dimensions do not include the Main Control Panel which can be mounted anywhere on the system perimeter or a nearby wall. Weight : Approx. 12,000 lbs. dry. (not inc. shipping crate).
|
| All of our acid wastes neutralization systems are completely fabricated and tested in our facility before shipping. Due to the size of the batchTREAT BT500 Acid Wastes Neutralization System the unit is shipped in three major modules: The two treatment tanks and the service support skid. | |
Digital
Analysis Corporation
PO Box 95
716 Visions Drive
Skaneateles, NY 13152
315-685-0760
315-685-0766(fax)
For Product Information : Email : info@digital-analysis.com